Подробное описание

Application

CJX2 series AC Contactor is suitable for using in the circuits up to the rated voltage 660V AC50Hz or 60Hz, rated current up to 620A, for making, breaking, frequently starting & controllingthe AC motor. Combined with the auxiliary contact block, timer delay & machine-interlockingdevice etc, it becomes the delay contactor, mechanical interlocking contactor, star-delta starter.With the thermal relay, it is combined into the electromagnetic starter. The product conforms toIEC60947-4-1 stardand.



Specification

TypeCJX2-D09CJX2-D12CJX2-D18CJX2-D25CJX2-D32CJX2-D40CJX2-D50CJX2-D65CJX2-D80CJX2-D95
Rated workingcurrent (A)AC39121825324050658095
AC43.557.78.51218.524283744
Standardpower ratingsof 3-phasemotors50/60Hz incategory AC-3220/230V2.2345.57.5111518.52225
380/400V45.57.5111518.522303745
415V45.5911152225374545
500V5.57.5101518.52230375555
660/690V5.57.5101518.53033374555
Rated heat current (A)2020324050608080125125
Electrical lifeAC3 (x104)100100100100808060606060
AC4 (x104)20202020201515151010
Mechanical life (x104)1000100010001000800800800800600600
Number of the contacts3P+NO3P+NC+NO







NORMALAUNNING AND INSTALLATION CONDITIONS

•Ambient air temperature:-5℃~+40℃, the average value should not exceed+35℃ within 24 hours. 

•Elevation:at most 2000m.

•Atmospheric conditions:When the temperature at 40, the relative humidity of atomsphere should be at the most 50%. When at relatively low temperatures, it could have higher relative humidity. Monthly maximum relative humidity could be not more than 90% . Special measures should be taken due to occurrence of dews.

•Class of pollution:Class 3

•Installation category: III

•Installation conditions:Degree of inclination between fitting surface and vertical surface should not exceed I

•Impact shock:Product should be installed and used in the place where often shakes and impacts.